A Guide To Describe The Occurrence and Mitigation
Of Switching Transients Induced By Transformer And
Breaker Switching Device Interaction
1.0 Overview
1.1 Scope
This Guide addresses the application of transformers in the presence of oscillatory switching transients.
These oscillatory transients are typically produced by the interaction of the breakerswitching device,
transformer, load, and system. This Guide defines operating conditions that may produce switching
voltages damaging to the transformers insulation system. It discusses the electrical characteristics of the
system source, breakerswitching device, transformer, and load and the nature of their transient interaction.
It outlines several mitigation methods. Two examples are included.
This Guide recognizes that many devices and/or system operations, in addition to breakerswitching
devicess, can produce the oscillatory transient waveforms addressed in this guide. The focus of this Guide
is on the transformer-breaker switching device interaction as a result of several reports of transformer
internal winding failures.
This guide focuses only on mechanical switching devices and do not cover semiconductor switching
devices.
1.2 Purpose
When a transformer is switched into or out of a system, the transient voltage produced at the terminals of
the transformer may contain a high frequency oscillatory component. When this oscillatory terminal
voltage has a frequency component near one of the natural frequencies of the transformer and is of
sufficient magnitude and duration, permanent damage to the transformer internal insulation structure may
result.
The purpose of this Guide is to provide aid in the recognition of condi