water example solution instructor水示例解决方案.pdf
a
XistWorkshop
Water-WaterExampleSolution
Instructor’sNotes
Objective
•Practicerunningacaseinsimulationmode,andinterprettheresults
CaseDescriptionandBackground
Thiscase(WaterWaterExample.htri)containsresultsforatypicalcomponentcoolingwaterservicefora
nuclearpowerplant.Thedesignmeetstheprocessspecificationswithservicewateronthetubeside
withtwopasses.Componentcoolingwaterisontheshellsideasthehotfluid.
Thefunctionofthisheateristoremovedecayheatofthereactorfollowingshutdown.The
dominantthermalresistanceisfoulingwhichistypicalforthisservice.Akeyrequirementforthisservice
isthatthecomponentcoolingwatertemperaturebereducedbelowacertainvalue24hoursafter
shutdown.Itipectedthattheerwillremovemorethanthedesigndutywhentheunitisnot
fouledtoitslimit.
Solution(Instructor)
•LoadWaterWaterExample.htri
oNotethepercentagethermalresistanceduetofouling(60%)
•Torunasimulationmodeundercleanconditions:
oRemovetheduty
oRemovethefoulingfactors
oSelectsimulationmode
•Runthecase
oXistwillcalculatetheumdutywhichcanberemovedunderthespecifiedinlet
temperatureconditions
•Warningmessages
oAninternaltemperaturecross
•PLOT:bulktemperaturesasafunctionoflength
oShowsthecross
•ResultsareshowninWaterWaterExample_1.htri
oDuty:5.02MW
•Thedesiredresultisadesignwhichavoidsthetemperaturecross.
•Oneposs