Installation Addendum: Filler Strip Gasket for Hot
Aisle Containment 23-in (750-mm) Ceiling Panels
Inventory
M6 × 60-mm screw (10) Ceiling panel filler-strip gasket (2)
Install the filler strip gasket
Apply the filler-strip gasket material to the outside edges of the ceiling panel frame to seal the gap
between two 23-inch rack ceiling panels, a 23-inch rack ceiling panel and the door frame, or a
23-inch rack ceiling panel and a 19-inch rack ceiling panel. Align the holes of the filler-strip gasket
material with the mounting holes on the frame.
a
6
5
3
1
a
n
Attach the ceiling panel to the door header or other ceiling panels using the ten M6 × 60-mm screws
provided.
Refer to the Hot Aisle Containment System installation manual that came with your system for the proper installation procedures.