2008 International Conference on High Voltage Engineering and Application, Chongqing, China, November 9-13, 2008
Analysis Of Low Reactance Grounding Protection
In 110KV Main Transformer Neutral System
Ping shaoxun, Zhou yufang, Zhang xuefeng
Rugao Electric power company Jiangs
Abstract- The paper summarizes produce over voltage oscillation, for connecting winding K is 1.6 and for
principle of 110KV main transformer central point and problem continuous winding K is 1.8; and ub is arrester’s residual
in protect mode ,suggest has grounding protection of low
voltage (or discharge voltage)at the transformer output.
reactance and this method could protect main transformer in
110KV transformer substation effectively。 Its maximum happens when lightning waves invade into
three-phase simultaneously. At this time, the value of over-
Key words- transformer ;over-voltage ;low reactance ;
voltage in nuetral point can be 1.6-1.8 times of arrester’s
protection ;grounding.
residual voltage in the transformer output. Regardless of
I. INTRODUCTION three-phase, two-phase or single-phase being invaded, the
atmosphere over-voltage is harmful to the neut