地基承载力试验检测频率.pdf
试验检测频率
一、地基承载力
1、挡墙基础:每侧每10延米至少检测2个点,必要时可根据需要增加检测点。
2、桥涵基础:每桥台至少检测6点,必要时可根据需要增加检测点。
二、地基承载力的计算(当用轻型触探仪检测时)
1、轻型触探仪(锤重10kg)检测地基承载力可按下列经验公式计算:
粘性土:σ0=(0.8N10-2)×9.8(Kpa)
砂性土:σ0=8.4N10-20(Kpa)
式中:σ0-实测地基承载力;
N10-锤重为10kg时的锤击数;
2、轻型触探仪(锤重10kg)检测地基承载力也可按经验公式查表:
地基承载力换算表(适用于粘性土)
地基承载力换算表(适用于粘性土)
锤击数0123456789
0-19.6-11.8-3.93.911.819.627.435.343.151.0
1058.866.674.582.390.298.0105.8113.7121.5129.4
20137.2145.0152.9160.7168.6176.4184.2192.1199.9207.8
30215.6223.4231.3239.1247.0254.8262.6270.5278.3286.2
40294.0301.8309.7317.5325.4333.2341.0348.9356.7364.6
50372.4380.2388.1395.9403.8411.6419.4427.3435.1443.0
60450.8458.6466.5474.3482.2490.0497.8505.7513.5521.4
注:根据锤击次数在表中纵向加横向相交处即为实测承载力(Kpa),如36次为262.6Kpa
地基承载力换算表(适用于砂性土)
锤击数0123456789
0-20.0-11.6-3.25.213.622.030.438.847.255.6
1064.072.480.889.297.6106.0114.4122.8131.2139.6
20148.0156.4164.8173.2181.6190.0198.4206.8215.2223.6
30232.0240.4248.8257.2265.6274.0282.4290.8299.2307.6
40316.0324.4332.8341.2349.6358.0366.4374.8383.2391.6
50400.0408.4416.8425.2433.6442.0450.4458.8467.2475.6
60484.0492.4500.8509.2517.6526.0534.4542.8551.2559.6
注:根据锤击次数在表中纵向加横向相交处即为实测承载力(Kpa),如36次为282.4Kpa
二、水泥砼抗压强度取样频率
评定水泥砼的抗压强度,应以标准养生28d龄期的试件为准。试件为边长150mm的立方体。
试件3个为1组,制取组数应符合下列规定:
(1)不同强度等级及不同配合比的砼应在浇筑地点或拌和地点分别随机制取试件。
(2)浇筑一般体积的结构物(如基础、墩台等)时,每一单元结构物应制取2组。
(3)连续浇筑大体积结构时,每80~200m3或每一工作班应制取2组。
(4)上部结构,主要构件16m以下应制取1组,16~30m制取2组,31~50m制取3组,
50m以上者不少于5组。小型构件每批或每工作班至少应制取2组。
(5)每根钻孔桩至少应制取2组,桩长20m以上者不少于3组,桩径大、浇筑时间很长时,
不少于4组,如换工作班时,每工作班应制取2组。
(6)构筑物(小桥涵、挡土墙)每座、每处或每工作班制取不少于2组。
(7)应根据施工需要,另制取几组与结构物同条件养生的试件,作为拆模、吊装、
张拉预应力、承受荷载等施工阶段的强度依据。
三、水泥砂浆抗压强度取样频率
评定水泥砂浆的抗压强度,应以标准养生28d的试件为准。试件为边长70.7mm的立方体。
试件6个为1组,制取组数应符合下列规定:
(1)不同强度等级及不同配合比的水泥砂浆应分别制取试件,试件应随机制取,不得挑选。
(2)重要及主体砌筑物