UNDERSTANDING ARC FLASH HAZARDS
Kevin J. Lippert Donald M. Colaberardino Clive W. Kimblin
Eaton Electrical Eaton Electrical Eaton Electrical
170 Industry Drive 170 Industry Drive 170 Industry Drive
Pittsburgh, PA 15275 Pittsburgh, PA 15275 Pittsburgh, PA 15275
ABSTRACT - The purpose of this paper is to clarify the their standard Code of Federal Regulations, CFR
[3]
use of the recently published IEEE 1584, “Guide for 1910.333, Selection and Use of Work Practices, which
Performing Arc-Flash Hazard Calculations.”[1] The paper states “Safety-related work practices shall be employed
also discusses the reduction of arc flash hazards by the to prevent electric shock or other injuries resulting from
current limitation of molded case circuit breakers. either direct or indirect electrical contacts, when work is
Understanding arc flash hazards is a critical element in performed near or on equipment or circuits which are or
order to reduce the risk of electrical accidents and personal may be energized.” This general statement provides
injuries. The Guide contains formulas to numerically the basis for OSHA’s citing and insisting upon
quantify the arc flash energy and includes an Excel compliance with the Arc Flash requirements contained
Spreadsheet “Arc-Flash Hazard Calculator.” This in NFPA 70E.
Spreadsheet