Instruction Manual C-453EM
SIGmA mOnITOR RELAy
Neutral Grounding Resistors (NGR) are an integral and critical
component in a grounding protection scheme and in many
ways are similar to fuses in that they nothing until something
in the system goes wrong. Then, like fuses, they protect
personnel and equipment from damage. Damage comes
from two factors, how long the fault lasts and how large the
fault is. Ground fault relays trip breakers to limit how long
a fault lasts. Neutral grounding resistors limit how large the
fault is.
The Sigma relay not only monitors the Neutral Grounding
Resistor to ensure its functionality and that it is available for
use but is also a ground fault relay.
DANGER
Hazard of Electrical Shock, Burn or Explosion
All installation, servicing and testing referred to in this manual must be performed by
qualified personnel.
All power shou