XJA1 Auto Voltage Reducing Starter
User Manual
Standard number:GB14048.4-2003Chang an Group Co. Ltd.
Ⅰ Outline
1. Applied as less frequent reduced-voltage starting for three-phase squirrel-cage induction motor of rated voltages and capacity up to and including 380V and 320kw, the starter minimizes the influence to the transmission network.
2. Working indoors and under following conditions:
Altitude ≤ 3200w
Temperature within -5℃and 40℃, with a 35℃average
Relative humidity under 85%
Amplitude≤0.5mm, frequency≤600/m
≤5°angle from the vertical
Neither in the environment with metal-corrosive or insulation-disturbing gas nor in the air with inductive or explosive dust.
Protection degree IP20
3. The model symbol is illustrated as follows:
X J A1 □
Ⅱ Starting Performance
4. To start an electric motor with XJA1, the starting current is 3-4 times over the rated and it should be done within 15 seconds. When using it twice in a roll, wait until it cools down to the room temperature, for frequent operation disturbs its performance.
Ⅲ Structure
5. XJA1 is designed as a central box structure, consisting mainly of an autotransformer, an AC contactor, a thermal relay, an intermediate relay, a time relay. Those up to 75kw apply automatic control system. Those 85kw and above apply two modes with an auto-man switch and an adjustable time relay, and starting time can be adjusted at between 5 and 15 seconds. There are two models of tapped coils, one with 65% rated voltage as the original default and an 80% one when necessary.
Ⅳ Technical Content
6. See Table 1 for technical content.
Model Rating
(kW) Max operating current Ie(A) Auto-transformer rating(KW) ratio(K) Relay setting current reference value(A) 7. The table above is only for reference. The setting value should be adjusted to the actual rating of the motor used. Change the thermal relay when necessary.
(1)set at Ie value for up to and 75kW
(2)set at XIe value for 80kW and abo