含小水电配电网线损问题的研究.doc
文本预览下载声明
含小水电配电网线损问题的研究
【摘 要】结合配电网实际情况,研究了含小水电电源线损高问题。基于改进等值电阻法给出 10kV 配电网理论线损计算算法,该算法计算结果准确度较高,而且更加符合实际,计算结果更加真实、准确,更能满足供电企业实际工作需要。同时给出了降低线损的具体措施,对提高供电企业的经营管理水平和经济效益具有明显的理论和现实意义。
【关键词】小水电;线损计算;改进等值电阻法;降损措施
Research of Line Loss Analysis for Distribution Power Network with Small hydroelectric power
CAO Wen-si1 HAN Ming-jun2 FAN Xiao-dong2 WU Xin-ning2
(1.North China University of Water Resources And Electric Power, Zhengzhou Henan 450011,China;
2.Luanchuan County Power, Luanchuan Henan, 471500,China)
【Abstract】According to the actual situation of distribution network, this paper discusses the problem of high line loss with small hydroelectric power. theoretical line loss calculation algorithm of 10kV Distribution network are given based on Improvement of the Method of Equivalent Resistance algorithm. The calculation results of higher accuracy, but also more practical, the result is more authentic, accurate, can better meet the actual work of power supply enterprises need. At the same time, Specific measures to reduce line loss is given, It has significant theoretical and practical significance to improve the power supply enterprises management level and economic benefits.
【Key words】Small hydroelectric power;Line loss analysis;Improvement of the method of equivalent resistance;Measure for reducing line loss
0 引言
随着能源问题和环境问题的日益突出,可再生能源利用逐渐得到国家重视,并已成为我国的重点发展战略之一。包括小水电在内的分布式发电具有投资小、清洁环保、占地小、供电可靠和发电方式可以对未来大电网提供有力补充和有效支撑,是未来电力系统的重要发展趋势之一[1-2]。
我国配电网复杂,小水电站并网运行,导致丰水并网与枯水停发时潮流分布差异很大,而网络结线和运行方式调整不尽合理,且小水电在丰水期往往存在着无功欠发,或在轻负荷时采取多发无功的方式来满足功率因数考核要求等原因,致使10kV配网线路电压不稳及线损高的问题增加,严重影响电网的经济运行[3-4]。
本文结合配电网实际情况,主要以传统配电网理论线损计算方法为主,为提高计算精度,对传统的等值电阻法进行改进,获得最佳计算方法。本文基于改进等值电阻法给出10kV配电网理论线损计算算法。1 改进等值电阻法的损耗计算方法
取配电线路上各节点月有功电量和无功电量,则电能损耗计算公式为:
△A=■■R■×10■
式中:△A为电能损耗(kWh);T为计算时段(h),取月小时数;A■为第i段线路上时间T内的有功电量(kWh);A■为第i段线路上时间T内无功电量(kvarh);R■第i段线路导线电阻(Ω);U■为对应于A■、A■处的电压(kV);n为该条线路导线的总段数。取配电线路月出口有功电量和无功电量,可以写成如下计算公式:
△A=■■R■×10■=■Rel×10■
式中:A■为月线路首端的总有功电量
显示全部