第8部分:配网工程
户外断路器、负荷开关安装作业指导书
编码:HWDQSB-01
目 次
1适用范围······················································································································································213
2编写依据······················································································································································213
3作业流程图··················································································································································213
4安全风险辨析与预控··································································································································213
5作业准备························································································································································13
6作业方法··························································································································································6
7质量控制措施及检验标准······························································································································9
1适用范围
1.1电压等级
35kV及以下配网工程。
1.2电气类别
配网工程中户外SF6断路器和真空断路器及负荷开关的安装。
2编写依据
表2编写依据
序号
引用资料名称
1
GB50173—1992《电气装置安装工程35kV及以下架空电力线路施工及验收规范》
2
Q/CSG11105—2008《南方电网工程施工工艺控制规范》
3
《中国南方电网有限责任公司基建工程质量控制作业标准(WHS)》
3作业流程图
4安全风险辨析与预控
图3作业流程图
4.1户外断路器、负荷开关安装作业前,施工项目部根据该项目作业任务、施工条件,参照《电网建设
施工安全基准风险指南》(下简称《指南》)开展针对性安全风险评估工作,形成该任务的风险分析表。
4.2按《指南》中与户外断路器、负荷开关安装作业相关联的《电网建设安全施工作业票》(编码:
HWDQSB-01-01/01),结合现场实际情况进行差异化分析,确定风险等级,现场技术员填写安全施工作业票,安全员审核,施工负责人签发。
4.3施工负责人核对风险控制措施,并在日站班会上对全体作业人员进行安全交底,接受交底的作业人员负责将安全措施落实到各作业任务和步骤中。
4.4安全施工作业票由施工负责人现场持有,工作内容、地点不变时可连续使用10天,超过10天须
重新办理作业票,在工作完成后上交项目部保存备查。
表4.1作业任务安全基准风险指南
序号
危害名称
风险种类
风险等级
风险控制措施
1
隔离开关、闸刀型开关处在断开位置时即开始搬运
打击
低风险
隔离开关、闸刀型开关应处在合闸位置才可以开始搬运
2
不按规定使用或选用不合格登高工具
坠落
特高的风险
按规定使用安全、合格的登高用具
3
高空作业不按规定佩戴安全带
坠落
特高的风险
使用双保险安全带
4
不用绳索传递工具、物料及不使用工具袋
打击
中等风险
用绳索传递工器具、材料,现场人员必须戴安全帽
5
用瓷套管作为受力点搬动开关
设备破损
中等风险
使用开关固定金属受力点搬运
6
线缆出入口封堵措施不足
设备停运
高风险
线缆敷设进入