±800kV东方换流站电气总布置方案设计.pdf
文本预览下载声明
2016
±800kV 东方换流站电气总布置方案设计
1 1 1 1 1 1
李扶中 孔志达 廖毅 张莉丽 王建武 郭金川
(中国能源建设集团广东省电力设计研究院有限公司,广东省广州市510663 )
GENERAL LAYOUT DESIGN FEATURES OF 800 KV DONGFANG
CONVERTER STATION
1 1 1 1 1 1
Li Fuzhong Kong Zhida Liao Yi Zhang Lli Wang Jianwu Guo Jinchuan
(Guangdong Electric Power Design Institute , Guangzhou city, 510663)
Abstract: The paper introduce ±800 kV UHV Dongfang 14 回,并且预留500kV 交流专用STATCOM 变
converter station from the electrical layout. Based on 压器1 组场地的设计方案,东方换流站围墙内
which, the original design of valve hall L layout and dc 占地仅为15.78 公顷,相比同等规模江门换流
field compact arrangement have carried on the thorough 站的21.65 公顷占地面积,少占地约5.87 公顷,
analysis of the characteristics. The optimization of the 节省了相当于6 个标准足球场的面积。[2]
scheme has strong practical value, which could raise the 作为工程方案的主要参与人和见证者,作
level of UHV design and provide a good reference model. 者较为全面地分析了东方换流站电气总平面布
置的设计特点。
Key word: DC transmission project UHV converter
station design feature 2. 工程建设规模
摘要:本文以滇西北至广东±800kV直流输电工程的受 东方换流站工程建设规模和主要技术参数
端东方换流站为论述对象,详细介绍了电气总平面布置 如下:
的主要设计原则,并对设计中采用的“阀厅L 型布置”、 直流输送功率为单极额定输送功率
“直流场紧凑型布置”等独创性设计方案进行了较为深 2500MW ,双极额定输送功率5000MW ;直流
入的特点分析。本文提出的优化方案具有较强的实用价 电压为额定电压±800kV;直流电流为额定电流
值,为提升我国的特高压直流输电自主设计水平提供了 3125A ;交流母线额定电压为525kV 。
每极有1 个高端阀厅和1 个低端阀厅,每
很好的参考范本。
个阀厅安装1 组12 脉动换流阀和6 台换流变,
关键词:直流输电工程 特高压换流站 设计特点 每台换流变的容量是237.4MVA ,全站共计
1. 引言 24+4 台换流变。