某局综合办公楼建筑给水排水工程设计.doc
文本预览下载声明
摘要
本设计的主要任务是天津市某建筑给水排水工程设计,设计的主要内容包括:建筑给水系统、建筑排水系统、消火栓给水系统和自动喷淋系统的设计。
市政给水管网MPa ,经技术经济比较,室内给水系统拟采用分区给水方式。分区:一至层为低区,由市政管网直接供水;层至十层为区,由变频泵供水。建筑排水系统采用合流制,
建筑消火栓给水系统主要为室内消火栓给水系统,消火栓的布置范围包括各楼层、消防电梯前室和屋顶检验用。消火栓保护半径为2m。
建筑内喷头数量约个,设报警阀,报警阀后管网为枝状网,每层设水流指示器。
关键词:
Abstract
The main task of this design is the water supply and drainage design of a business buiding in Tianjin. The content of my design includes the design of the building water supply system, the building water drainage system, the building storm-water system, the hydrant water supply system and the automatic sprinkler system.
The building has 1 floor underground and 25 floors overground. The height of the building is92.9m.The first to the fourth floor are Non-standard layer; The fifth to the twenty five are standard layer;The twenty-fifth is the top.
The municipal water supply piping can provide 0.25Mpa head. After the comparison of technicality and economy, interior water supply system intends to adopt subarea water supply. Preliminary study out that building water supply system is divided three areas: -1~3 floors are low area. The pipe network supplies water directly from municipal water supply piping;4~13 floors and 14~25 floors are high area. Water supply is supplied by no negative pressure water equipment.
The building water sewerage system adopt confluence .All waste water enter drain via a septic-tank.The building storm-water system adopts inner draining.
Hydrant water supply system includes interior hydrant water supply system and outside hydrant water supply system. Hydrant arranging range includes every storey, the room in front of fire elevator and roof for check. The hydrant protects a radius of 23m.
The number of sprinkler heads in the building is about 3328. The automatic sprinkler system set up 5 groups watery alarm valve. Behind the alarm valve, the piping is set as branch. Every storey set water flow indicator.
Key words:the building water supply system;water drainage system;hydrant water supply