LCM1500 Power Supply.pdf
文本预览下载声明
POWER
LCM1500
1500 Watt Bulk Front End
Total Power: 1500 W
# of Outputs: Single
Outputs: 12 to 48 V
Optional 5.0 V standby
SPECIAL FEATURES
? 1500 W output power
? Low cost
? 2.5” x 5.2” x 10.0”
? 12 Watts per cubic inch
? Industrial/Medical safety
? -40 °C to 70 °C with derating
? Optional 5 V @ 2 A
housekeeping
? High efficiency: 89% typical
? Variable speed “Smart Fans”
? DSP controlled
? Conformal coat option
? ± 10% adjustment range
? Margin programming
? OR-ing FET
COMPLIANCE
? EMI Class A
? EN61000 Immunity
? RoHS 2
SAFETY
? ULcUL Recognized ITE
(UL60950-1)
? ULcUL Recognized Medical
(ANSI/AAMI ES60601-1)
? TUV-SuD ITE + Medical
(EN60950-1 and EN60601-1)
? CE LVD (EN60950-1 + ROHS)
? BSMI
? CB Report
- through Demko for IEC60950-1
- through TUV-SuD for
IEC60601-1
Electrical Specifications
Input
Input ra nge 90 - 264 Vac (Operating)
115/230 Vac (Nominal)
TERMINAL BLOCK
Frequency 47 - 440 Hz, Nominal 50/60
Input fusing Internal 20 A fuses, both lines fused
Inrush current ≤ 25 A peak, either hot or cold start
Power factor 0.99 typical, meets EN61000-3-2
Harmonics Meets IEC 1000-3-2 requirements
Input current 18 A RMS max input current, at 100 Vac
Hold up time 20 ms minimum for Main O/P, at full rated load
Efficiency 91% typical at full load / 230 Vac nominal
Leakage current 0.4 mA at 264 Vac
ON/OFF power switch N/A
Power line transient MOV directly after the fuse
Isolation PRI-Chassis 2500 Vdc Basic
PRI-SEC 4000 VAC Reinforced 2xMOPP
SEC-Chassis 500 Vdc
LCM1500Q Efciency Without the 5 Vsb
76.00
78.00
80.00
82.00
84.00
86.00
88.00
90.00
92.00
25 50 75 100
Loading %
E
f
c
ie
n
c
y
%
100 Vac
230 Vac
Data Sheet
LCM1500 Data Sheet
Environmental Specifications
Operating temperature: -40 °C to +70 °C, linear derating to 50% from 50 °C to 70 °C
Storage temperature: -40 °C to +85 °C
Humidity: 20 to 90%, non-condensing. Operating. Conformal coat option available
Fan noise: 45 dBA, 80% load at 30
Altitude: Operating - 16,405
显示全部