ABB NOCH 滤波器选型手册.pdf
文本预览下载声明
ABB Industry Oy
Drives Products
Instruction 3AFE xxxxxx
dudt filter selection guide.DOC
Dept.
EJQ
Date
29.12.1998
Made by
Marko
Ven?l?inen
Checked / Accepted by
Matti Laitinen
Revision
E
Page
1 / 12
Effective: 29.12.98
Supersedes:03.04.98
ACS600 DU/DT FILTER SELECTION GUIDE
Output voltage of ACS600 2
Peak voltage and du/dt at the motor terminals 2
Voltage vaweform 3
Applicable motors according to the service life of the insulation system 5
Random wound motors 5
Form wound motors 5
du/dt filters 6
The enclosure class of the filters 6
A guide for adding the filter option to an Acknowledgement of Order 6
Notes on installation of du/dt filter KITs 7
Standard applications 7
Other applications 9
Pull-out torque with du/dt filter 11
EMC 12
CE 12
Bearing currents 12
APPENDIX 1: du/dt Filter Installation Guide 12
ABB Industry Oy
Drives Products
Instruction 3AFE xxxxxx
dudt filter selection guide.DOC
Dept.
EJQ
Date
29.12.1998
Made by
Marko
Ven?l?inen
Checked / Accepted by
Matti Laitinen
Revision
E
Page
2 / 12
Effective: 29.12.98
Supersedes:03.04.98
Output voltage of ACS600
Peak voltage and du/dt at the motor terminals
The output voltage waveform of an inverter creates voltage spikes at the motor terminals in excess
to dc-bus voltage. The combination of these voltage spikes and high du/dt-value of IGBT inverter
output means additional stresses to motor insulation. This may shorten the life of the motor.
In the graphs below the peak value ? LL and the rate of change du/dt of the voltage mesured at the
motor terminals are seen as a function of the motor cable length. ? LL is scaled to nominal line-to-
line voltage ULLnom. The scale of du/dt is kV/μs.
The values of the graphs are typical values measured for ACS600 feeding a nominal load (Udc ?
1.35* ULLnom ) to a rated motor. In case of regenerating or braking the value of ? LL is appr. 20 %
higher.
The values seen in the first graph are mesured without any output filtering. In the second graph the
values are measured w
显示全部