第29 卷第1 期 建 筑 热 能通 风 空 调 Vol.29 No.1 2010 年2 月 Building Energy Environment Feb. 2010.80~82 文章编号:1003-0344(2010)01-80-3 北方寒冷地区医院洁净手术室供暖节能分析 张润斌 蔡觉先 兰州交通大学环境学院 摘 要:本文运用CFD 技术作为辅助工具观察热水采暖系统对医院四级手术室气流组织的影响,研究中采用了 k-ε 模型,并用FLUENT 软件进行求解。最后在实地进行实验数据采集,进一步验证软件模拟结果的正确性。在满 足国家规范的基础上,探讨了北方地区热水采暖取代热泵空调机组加电采暖的可行性。 关键词:手术室气流组织 CFD 湍流模型 Heat ing in t he Cleanroom of Hospit al in Nort h China ZHANG Run-bin, CAI Jue-xia College of Environmental Science, Lanzhou Jiaotong University Abst ract : This paper illustrated how to use the CFD method as an assistant tool to make a research of the way of hot-water heating in the Ⅳ cleanroom, which probably has an effect on airflow pattern. The Reynolds-averaged Navier-Stokes equations were solved using a finite-volume method. Different plans were established for the cleanroom and simulated by the FLUENT software. It was compared to the data which comes from field experiment. Finally, a concern was attached to the possibility of applying hot-water heating to replace the traditional heating way. Keywords: cleanroom, airflow pattern, CFD, turbulent model 目前,国内研究洁净室手术净化空调系统节能的 得出的数据来验证《医院洁净手术部建筑技术规范》中 措施有很多,包括选择二次回风空气处理过程、洁净 关于四级手术室采用热水采暖方式供暖(采用安装有 手术室的正压控制等,但很少有从冬季供暖的方式上 温度监测器和热水流量控制阀,并由自动控制系统来 是否节能的角度进行探讨的文章。随着建设部颁发的 控制热水流量的方式,从而实现温度的恒定)的可行 [1] 《公共建筑节能设计标准》 开始实施,国家对新改建 性,并进一步对散热器置于手术室不同位置的模拟,观 的公共建筑提出了节能要求。针对医院手术部空调净 察其对手术室回风口等处气流是否构成影响(手术室 化系统能耗高的问题,本文讨论了在北方寒冷地区采