摘要:针对电力系统内 110 kV 及以上变电站主变压器有载调压机构在档位调节过程中出现的无法正常闭锁有载调压机构、
无法正常调档等缺陷,按照主变压器有载调压功能的设计原理对有载调压控制回路中存在的不足之处进行了详细的分析,判
断出缺陷的发生是因为有载调压控制回路设计有误造成的。针对此缺陷,提出了如何正确改进、完善主变压器有载调压控制
回路的有效措施。
关键词: 过负荷闭锁有载调压; 测控装置; 有载调压档位控制器
Improvement for the coaded voltage adjustment and control loop of the main transformer
FU Wen-zhu
(Henan Hebi Power Supply Company, Hebi 458030,China)
Abstract: The loaded voltage adjustment construction of the main transformers in substations of 110 kV and above have in the files
position adjustment process some defects, e.g. being unable to block the loaded voltage adjustment construction normally, being not
able to normally shift gears etc. According to the designing principle of the loaded voltage adjustment function of main transformers,
it analyses detailedly the above mentioned defects and states that the reason of the defects is the designing mistake of the loaded
voltage adjustment and control loop. Upon that, some effective measurements for its improvement and perfection are given.
Key words: overload atresia OLTC; measuring devices; OLTC stalls controller
中图分类号: TM76 文献标识码: B 文章编号: 1003-4897(2008)04-0079-02
主变压器保护配置中设置有过负荷闭锁有载调
0 引言
压功能,当变压器过负荷运行禁止有载调压档位操作
随着我国电力网架的不断完善,不断坚强, 时,此保护可以有效地防止主变压器有载档位的异常
高压及超高压变电站已经占据了主导地位,但是在 操作。在 110 kV 及以上变电站主变压器有载调压控
110 kV 变电站和部分 220 kV 变电站,继电保护二 制回路设计中,总体分为两种配置:第一种是测控装
次回路还存在设计不规范、不统一、回路有缺陷等 置直接控制主变压器有载调压机构(图 1);第二种
诸多不足,也严重影响了电力系统的安全运行。
显示全部