GT-FluxFP-D-使用说明书手册_EN.pdf
OPERATINGINSTRUCTIONS
GT-FluxFP-D
OrificePlateFlowmeter
FMApproved
GT-FluxFP-D-Manual-ENRev.0
IMPRINT
Allrightsreserved.Anyreproductionorusagewithoutwrittenauthorisation
ofTornatechInc.-evenpartialcontent-isstrictlyprohibited.
Subjecttochangewithoutnotice.
Copyright2024byTornatechInc.
2GT-FluxFP-D-Manual-ENRev.0
TableofContents
1 SAFETY INSTRUCTIONS4
1.1 Intended use4
1.2 Certifications5
1.3 Safety instructions of the manufacturer5
2 SCOPE OF THE DEVICE6
2.1 Included with the device6
2.2 Type plate7
3 INSTALLATION AND MODE OF OPERATION8
3.1 Information about installation8
3.2 Installation8
3.3 Mode of operation9
3.4 Electrical connection9
3.5 Overview of operating element functions11
3.6 Settings12
4 PREPARATION FOR OPERATION14
4.1 Ambient conditions14
5 SERVICE14
5.1 Storage14
5.2 Maintenance14
5.3 Returning the meter back to the manufacturer15
5.4 Disposal15
GT-FluxFP-D-Manual-ENRev.03
SAFETY INSTRUCTIONS
1SAFETY INSTRUCTIONS
1.1Intendeduse
The GT-FluxFP-D orifice flow meter – consisting of a measurement orifice and a bypass
flow meter – serves to measure the volume flow of water in test pipes of water supply sys-
tems in stationary water extinguishing systems.
The microprocessor-controlled GT-FluxFP-D indicator described here can be used as an
alternative to the mechanical bypass flow meter. Using the operating unit on the device,
the nominal size and rated power of the pump can be adjusted to match the individual
system properties. The digital indicator registers and processes the measurement signals
from the associated measurement orifices of the GT-FluxFP-D series. In addition to the
visual display, the device also ha