CAPACITIVE VOLTAGE TRANSFORMERS
Capacitive Voltage Transformers (CVTs) are common in high-voltage transmission line applications. These same applications require fast, yet secure protection. However, as the requirement for faster protective relays grows, so does the concern over the poor transient response of some CVTs for certain system conditions.
Solid-state and microprocessor relays can respond to a CVT transient due to their high operating speed and increased sensitivity .This paper discusses CVT models whose purpose is to identify which major CVT components contribute to the CVT transient. Some surprises include a recommendation for CVT burden and the type of ferroresonance-suppression circuit that gives the least CVT transient.
This paper also reviews how the System Impedance Ratio (SIR) affects the CVT transient response. The higher the SIR, the worse the CVT transient for a given CVT .
Finally, this paper discusses improvements in relaying logic. The new method of detecting CVT transients is more precise than past detection methods and does not penalize distance protection speed for close-in faults.
INTRODUCTION
Poor CVT transient response and the distance element overreach it causes are a serious concern for high-speed line protection.
For faults that cause very depressed phase voltages, the CVT output voltage may not closely follow its input voltage due to the internal CVT energy storage elements. Because these elements take time to change their stored energy , they introduce a transient to the CVT output following a significant input voltage change. In this paper, we define the duration of CVT transient as that time period during which the CVT output voltage does not match the ratio input voltage.
This paper addre